JOB SITE OBSERVATIONS
Starlight Towers-Building Restoration
KEG FILE #07-RP-0453
Permit # 20080229
April 30th, 2008
   
INDIVIDUALS PRESENT:
          Santiago Bartolome, Karins Engineering Group, Inc. (KEG)
          Norman Bavis, Complete Property Services.

ARRIVED: 13:00                                                                                  Report #07
DEPARTED: 14:30
WEATHER: Sunny


As requested, an engineer from Karins Engineering Group, Inc. (KEG) visited the Starlight Towers Building Restoration project to observe the repairs-in-progress. The purpose of our observations was to verify general conformance with the project specifications and to record quantities for unit cost work.
 
The following items were observed:
  • Partially inspected precast concrete joists and the underside of the slab on the 10" floor walkway. Joists appear to be severely deteriorated.
    • Joists must be properly shored prior to further excavation.
    • Joists must be excavated until sound concrete is found.
  • Partially inspected precast concrete joists and the underside of the slab on the 9" floor walkway. Joists appear to be severely deteriorated.
    • Joists must be properly shored prior to further excavation.
    • Joists must be excavated until sound concrete is found.
  • Inspected excavated areas on North stairwell.
    • Spalls created by corrosion of reinforcing steel must be excavated to sound concrete and clean steel.
    • Deteriorated conduits must be replaced and area properly repaired.
    • Structural cracks running along the CMU walls must be "V" notched and filled with epoxy in accord with Section 03300.

With the exceptions noted above, work appeared to be progressing in general accordance with the requirements of the Project Manual.
 
Photos attached for your review.


  Copies:
Vance Poland
Michael Krueger
Marlene Reid
    (Signature)
F. Carter Karins, P.E.
Florida Registration #62446
C.E.O.
 
  Florida Certificate of Authorization Number 8371
St. Petersburg, FL Sarasota, FL - Main Office Naples, FL / Ft. Myers, FL

(webmaster's note: Original picture quality was very poor. I tried to enhance as best as possible)

 

IMG 0126 - 4/30/2008 1:01:17 PM

 

IMG 0127 - 4/30/2008 1:01:19 PM

 

IMG 0128 - 4/30/2008 1:10:18 PM - Joist on 10th floor

 

IMG 0129 - 4/30/2008 1:16:28 PM - North stairwell excavated issues

 

IMG 0130 - 4/30/2008 1:16:40 PM - North stairwell excavated issues

 

IMG 0131 - 4/30/2008 1:16:49 PM - North stairwell excavated issues

 

IMG 0132 - 4/30/2008 1:17:35 PM - North stairwell excavated issues

 

IMG 0133 - 4/30/2008 1:18:53 PM - North stairwell excavated issues

 

IMG 0134 - 4/30/2008 1:18:56 PM - North stairwell excavated issues

 

  

IMG 0135 - 4/30/2008 1:19:15 PM - North stairwell excavated issues 

 

IMG 0136 - 4/30/2008 1:19:59 PM - North stairwell excavated issues

 

IMG 0137 - 4/30/2008 1:25:52 PM - Level 9 joist and slab deterioration

 

IMG 0138 - 4/30/2008 1:26:00 PM - Level 9 joist and slab deterioration

 

IMG 0139 - 4/30/2008 1:32:56 PM - Level 9 joist and slab deterioration

 

IMG 0140 - 4/30/2008 1:33:17 PM - Level 9 joist and slab deterioration

 

IMG 0141 - 4/30/2008 1:33:51 PM - Level 9 joist and slab deterioration

 

IMG 0142 - 4/30/2008 1:35:16 PM - North stairwell issues

 

IMG 0143 - 4/30/2008 1:35:58 PM - North stairwell issues

 

IMG 0144 - 4/30/2008 1:40:43 PM - North stairwell issues

 

IMG 0145 - 4/30/2008 1:42:08 PM - North stairwell issues

 

IMG 0146 - 4/30/2008 2:06:53 PM - Lintel damage on Unit 808

 

IMG 0147 - 4/30/2008 2:06:57 PM - Lintel damage on Unit 808

 

IMG 0148 - 4/30/2008 2:07:00 PM - Lintel damage on Unit 808

 

IMG 0149 - 4/30/2008 2:07:04 PM - Lintel damage on Unit 808

IMG 0150 - 4/30/2008 2:08:40 PM - Lintel damage on Unit 808

 

IMG 0151 - 4/30/2008 2:30:54 PM

 

IMG 0152 - 4/30/2008 2:31:01 PM

 

 
Molon Lave Semper Fidelis
  Starlight Tower St Pete Beach Florida picture from Gulf BoulevardStarlight Tower St Pete Beach Florida picture from the Gulf of MexicoView from the South fence of Starlight Tower at St Pete Beach Pinelas County FloridaStarlight Tower's swimming poolRainbow at Starlight Tower St Pete Beach, Florida on Blind Pass sideStarlight Tower St Pete Beach Florida  
The site's mission: Is to keep informed absent Starlighters of all important issues and events taking place in our property. Is nourished continuously with fresh information generously provided by resident fellow Starlighters and not only offers a private meeting place for owners but is helpful to the public regarding local events taking place in our town St. Pete Beach Pinellas County Florida as well as attractions, accommodations and places of interest to families, couples and individuals. Please e-mail your textual and multimedia materials for inclusion in our website to Louisa Simos: webmaster@starlight-tower.com
Copyright 2006-2015 www.starlight-tower.com All rights reserved. Questions email to: webmaster 
Co-op's Physical Address: 7000 Beach Plaza, St Pete Beach, Florida 33706 Office Tel: 727-360-8820